• Company News

Consulting Services

  • Fire Protection, Life Safety, and Accessibility Code Consulting
  • Healthcare Specialty Consulting
  • NFPA 241, Construction Fire Safety, Permitting and Turnover Consulting
  • Laboratory / Industrial / Hazardous Chemical Compliance Consulting
  • Battery & Energy Storage System Fire Safety

Inspection, Testing & Commissioning

  • Fire Door Testing and Inspections
  • Firestop Special Inspections
  • Life Safety System Re-Commissioning & Retro-Commissioning
  • NFPA 3, Fire Protection System Commissioning and NFPA 4 Integrated Fire Protection and Life Safety System Testing
  • Smoke Control Special Inspections

System Design

  • Fire Alarm System Design
  • Performance-Based Design
  • Smoke Control System Design
  • Fire Protection System Design
  • Third Party Reviews

Code Red Consultants

Back to Insights

Measuring Exit Access Travel Distances

October 10, 2022 by Nick Ostrowski

The exit access configuration within a building is impacted by multiple code requirements to ensure that occupants can safely reach an exit and continue to the exit discharge. One of the major limitations that is required to be evaluated when configuring the exit access arrangement is Exit Access Travel Distance. Exit Access Travel Distances are limitations that identify the maximum distance from any point of a story to an exit. These are measured along the exit path from the most remote point of a story along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit (2015 IBC 1017.3). An exit can include exterior exit doors at the level of exit discharge, interior exit stairways and ramps, exit passageways, exterior exit stairs and ramps and horizontal exits.

Although IBC Section 1017.3 and NFPA 101 Section 7.6 outline how this measurement is taken, there are some common questions raised specific to this process given the different components exit access configurations consist of. The following include a few clarifications to address some these misconceptions while measuring Exit Access Travel Distances:

  • Travel Distances are measured to the nearest exit , not all exits. The most remote point on the floor is required to be within the exit access travel distance limitations to any one exit on the floor.
  • Often, travel distances change throughout the design of a project. Introducing new furniture or wall partitions for a tenant fitout or alternate furniture layout on a floor may obstruct an existing exit access path. As a result, the new exit access path could exceed the maximum travel distance beyond what is permitted. As design changes take place, it should be confirmed that compliant exit access travel distances are maintained.
  • If an exit access stairway or ramp is provided along the path of travel, the Exit Access Travel Distance includes the travel down the exit access stairway/ ramp. The measurement along exit access stairways is required to be made on a plane parallel and tangent to the stair tread nosing’s in the center of the stair and landings. The measurement along ramps is required to be made on the walking surface in the center of the ramp and landings.

It is important to understand how to measure exit access travel distances. If you have any questions on or concerns about this information, please contact our office at [email protected] .

Application of any information provided, for any use, is at the reader’s risk and without liability to Code Red Consultants. Code Red Consultants does not warrant the accuracy of any information contained in this blog as applicable codes and standards change over time. The application, enforcement and interpretation of codes and standards may vary between Authorities Having Jurisdiction and for this reason, registered design professionals should be consulted to determine the appropriate application of codes and standards to a specific scope of work.

Related Posts

EGRESS – PART 3 10th Ed. MA Code Changes

Elevator Means of Egress

Horizontal Exits Design Considerations

maximum exit access travel distance

  • Search forums
  • Welcome to the new and improved Building Code Forum. We appreciate you being here and hope that you are getting the information that you need concerning all codes of the building trades. This is a free forum to the public due to the generosity of the Sawhorses, Corporate Supporters and Supporters who have upgraded their accounts. If you would like to have improved access to the forum please upgrade to Sawhorse by first logging in then clicking here: Upgrades
  • Commercial Codes
  • Commercial Building Codes

Egress travel distance for two exits

  • Thread starter Mech
  • Start date Aug 26, 2010

Registered User

  • Aug 26, 2010

IBC 2006 / 9 From the most remote point, one must travel a distance less than the common path of egress travel before choosing which route to take to exit a building. Must both exits, measured from the most remote point, be within the maximum travel distance? I am thinking the answer is yes.  

Examiner

The travel distance is to ONE EXIT. If the travel is say 200-ft to an (mono) EXIT then the EXITS can be 400-ft apart as the crow flies. I go from the remote point in a room to the exit by using a L-shape out of the first room then the rest of the way can be a route that is as straight as possible if there are no items in the way to go around to the exit. Then from the adjacent room that the first was checked you go the other way to the second exit. You do not have to have both rooms to reach the same exit. I hope this makes sense, I can draw it better than describe it.  

Builder Bob

Builder Bob

Basically yes............ As always, this is a ROT and your specific application may vary from other AHJ interpretations.  

I know the travel distance is to one exit. Must the second exit also have a travel distance less than the maximum allowed? Suppose the maximum allowable travel distance is 200 ft. If I exit a room and turn right, assume the first exit is 198 ft from the most remote point in that room. 198 < 200 - exit is good. If I exit that same room and turn left, assume the only other exit is 250 ft from the most remote point in that room. 250 > 200. Does this qualify as a second exit for this room since the travel distance exceeds the maximum allowed? BTW Examiner, one more post and I bet you'll achieve "silver" member status!!!  

Platinum Member

1016.1 : "The maximum length of exit access travel...to AN ... exit". Just make sure every portion that needs two exits is within the required travel distance to at least one of the exits.  

deleted. a duplicate appeared  

As others stated, ONE exit is required within the allowable travel distance. The travel distance to the second, third, or fourth exit(s) is not regulated.  

and if the fire blocks the exit within the allowable travel distance?  

  • Aug 27, 2010

Then you die in a building that meets code. Or you move calmly but briskly a little further to get to the second exit.  

If you are in one room and from that room's the exit travel is max you are ok. Even if you have another EXIT farther away. If that one room meets the max travel distance and the adjacent room does not then the adjacent room must have AN exit within the required EXIT TRAVEL DISTANCE. There are only a few instances where you can have one exit and that is limited to travel distane less than the normal EXIT Travel, story height and occupant load. You will most always have two eixts and each room in a building with two EXITS must reach AN (ONE) (Mono) EXIT within the required travel distance.  

peach said: and if the fire blocks the exit within the allowable travel distance? Click to expand...

Mech - Valid concerns, however, the codes are a minimum... what you are posing or suggesting were certainly be desired but cannot be required by the minimums of the code.  

  • Codes and Standards

The IBC’s modification to exit access travel distance

Understanding the international building code’s increase for group f-1 and s-1 occupancy..

The 2015 International Building Code includes a key modification, increasing the length of exit access travel distance from 250 ft to 400 ft (if it meets specific criteria) for buildings containing Group F-1 and/or S-1 occupancy.

This change is significant to the design industry, building owners and occupants of large distribution and manufacturing facilities. Understanding the code’s implications for your existing and future facilities will ensure you’re properly prepared. A brief timeline of exit access travel distance

  • 1994: In the 1994 Uniform Building Code, the exit access travel distance in a building protected with a fire sprinkler system was typically 200 ft. The exit access travel distance could be increased to 400 ft when facilities storing or manufacturing noncombustible products were provided with smoke/heat vents in addition to the fire sprinkler system.
  • 1997: In the 1997 Uniform Building Code, this section was revised to allow this increase to apply to all warehouses and factories if they were protected with a fire sprinkler system and smoke/heat vents. This exit access travel distance increase resulted in larger buildings with open, undivided areas. A typical warehouse ranged from 600 to 700 ft wide. As buildings continued to grow, 600 ft became the narrow dimension for a warehouse, with many buildings exceeding 1000 ft in length.
  • 2009/2012: The 2009/2012 editions of the International Building Code were revised to eliminate the 400 ft exit travel distance for large Group S-1 warehouses and large Group F-1 manufacturing facilities equipped with smoke and heat vents. This change was made because thermally activated vents were judged not to warrant such an increase.

The effects of eliminating the 400 ft exit travel distance

Due to the 400 ft loss, designers had to modify new warehouse and manufacturing facilities’ proportions or incur the cost of providing additional exits. And while it was clear to many in the industry that the original rationale for 400 ft was faulty, eliminating the requirement in its entirety was not an option.

The industry focused on ways to increase the travel distance for large buildings containing Group F-1 and/or S-1 occupancy.

Task group 400

An industry group in California came together as "Task Group 400" and conducted a fire modeling study, which demonstrated that the vast volume of large buildings could be used to contain smoke.

The group’s report was reviewed by the California State Fire Marshal’s Office and presented to the California Building Standard Commission, requesting a reinstatement of the 400 ft travel distance without any special protection, provided all of the following are met:

1. The portion of the building classified as Group F-1 or S-1 is limited to one story in height.

2. The minimum height from the finished floor to the bottom of the ceiling or roof slab or deck is 24 ft.

3. The building is equipped throughout with an automatic fire sprinkler system in accordance with section 903.3.1.1.

The exit access travel distance reversal was successfully passed, and California adopted an amended version of the 2009 International Building Code as the 2010 California Building Code.

California’s code change was later adopted into the 2015 edition of the International Building Code – the model code for most states.It should be noted that, although code no longer requires smoke and heat vents for this travel distance increase, vents or mechanical smoke removal system, are still required by Section 910.3 and 910.4  for Group S-1 and F-1 buildings of more than 50,000 sq ft. There are exceptions, however, for frozen food warehouses and areas with specific types of sprinkler systems.

Sonja Antunovic-Curcic has over 15 years of experience in architectural design. She has a strong technical background and ability to effectively transform challenges into opportunities. Her experience involves design of new buildings, expansions or alterations to existing buildings. This article originally appeared on Stellar Food for Thoughts . Stellar is a CFE Media content partner. Edited by Joy Chang, digital project manager, CFE Media, [email protected]

Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our CFE Media editorial team and getting the recognition you and your company deserve. Click here to start this process.

  • Use NFPA 3 for new, existing buildings
  • Reviewing the 2014 NEC
  • Fire and life safety: Six trends that matter to engineers

Related Resources

Privacy overview.

ARCH 2614/5614 Building Technology I: Materials and Methods

contact | office hours

Refer to Chapter 10, IBC 2012 and "Egress" chapter of The Architect's Studio Companion, by Allen and Iano (course reserve).

Means of egress is continuous and unobstructed path of travel from any point in a building to a public way. It consists of 3 basic parts:

exit access (including corridors)

exit (basically the enclosed stair)

exit discharge (which leads to the public way)

Table 1017.2 Exit access travel distance

maximum exit access travel distance

Table 1006.2.1 Common path of egress travel (Scroll down to Table 1006.2.1, 2020 NYS Building Code, based on 2018 IBC)

Section 1020.4 Dead-end corridors (Scroll down to Sec. 1020.4, 2020 NYS Building Code, based on the 2018 IBC)

maximum exit access travel distance

Notes on egress:

generally no elevators * or escalators allowed (except as "accessible means of egress" in some circumstances): if unsprinklered, such elevator access must be from "area of refuge" or "horizontal exit."

"The Fire, Buildings and City Planning Departments [in NYC] are writing rules to govern what are called occupant-evacuation elevators — cars that can, in special circumstances, be used to move people down in an emergency."

"That would upend decades of codes and practices based on the notion that elevators are perilous and undependable in fires or other emergencies. Experts who have spent years studying building evacuations believe that approach has become outmoded and is in itself potentially dangerous as extremely tall skyscrapers increasingly pierce the New York skyline."

"Some requirements that the city is expected to impose for evacuation elevators have been anticipated in elevators at 3 and 4 World Trade Center. The floors in front of the elevator doors are raised slightly, to protect the hoist ways from water from sprinklers or firefighters' hoses. The capacity of the emergency generators was increased to provide uninterrupted service to those cars. The cars stop at every floor. Hoist ways are within cores protected by reinforced concrete walls at least 18 inches thick." [ NY Times, March 18, 2015 ]

provide guards where a floor surface is more than 30" above floor below; such guard rails are 42" high (except 36" in R-3 occupancies), and configured so that a 4"-diameter sphere cannot pass through.

need 2 means of egress for most buildings (1 for very low occupancies; 3 for 501-1000 occupants; 4 for more than 1000 occupants). Compute number of occupants by dividing floor area by "design occupant load" in code.

spaces with one means of egress permitted generally have a maximum occupancy of 49, except that number is only 3 for H-1, H-2, H-3; and 10 for H-4, H-5, I-1, I-3, I-4, R; and 29 for S occupancies)

buildings allowed one means of egress have similar occupant limits but also have maximum numbers of stories (generally 1 story maximum, except 2 for R-2 occupancies, 3 if sprinklered); plus maximum travel distances to exits.

maximum exit access travel distance

typical minimum door size is 36" (which is also the most common door size for both egress and accessibility).

maximum exit access travel distance

techniques to keep smoke out of egress stairs: smokeproof enclosures can be exterior "balconies" separating the entrance to the stair from the occupied space and providing a means for smoke to be exhausted to the exterior before entering an enclosed stair; or they can use ventilation ducts provided for that purpose; or, in certain cases; stairs can be mechanically pressurized so that smoke doesn't enter.

Disclaimer: Students are responsible for material presented in class, and required material described on course outline. These notes are provided as a tentative outline of material intended to be presented in lectures only; they may not cover all material, and they may contain information not actually presented. Notes may be updated each year, and may or may not apply to non-current versions of course.

Copyright 2007–2021 J. Ochshorn. All rights reserved. Republishing material on this web site, whether in print or on another web site, in whole or in part, is not permitted without advance permission of the author.

IMAGES

  1. AC 029

    maximum exit access travel distance

  2. Clause 2.2 Determinations of Exit Requirements

    maximum exit access travel distance

  3. Unraveling the City of Los Angeles 150' Fire Access Travel Distance

    maximum exit access travel distance

  4. Exit Travel Distance

    maximum exit access travel distance

  5. Going the Distance

    maximum exit access travel distance

  6. Exit Travel Distance

    maximum exit access travel distance

COMMENTS

  1. 2018 International Building Code (Ibc)

    The maximum travel distance from any accessible space to an area of refuge shall not exceed the exit access travel distance permitted for the occupancy in accordance with Section 1017.1. 1009.6.2 Stairway or elevator access.

  2. Measuring Exit Access Travel Distances

    Exit Access Travel Distances are limitations that identify the maximum distance from any point of a story to an exit. These are measured along the exit path from the most remote point of a story along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit (2015 IBC 1017.3).

  3. Travel Distance Limitations

    200 c. For SI: 1 foot = 304.8 mm. See the following sections for modifications to exit access travel distance requirements: Section 402.4: For the distance limitation in malls. Section 404.9: For the distance limitation through an atrium space. Section 407.4: For the distance limitation in Group I-2.

  4. Exit Access Travel Distance

    404.9 Exit Access Travel Distance. Illinois Building Code 2021 > 4 Special Detailed Requirements Based on Occupancy and Use > 404 Atriums > 404.9 Exit Access Travel Distance. Go To Full Code Chapter. Exit access travel distance for areas open to an atrium shall comply with the requirements of Section 1017.

  5. Chapter 4: Accessible Means of Egress

    Accessible means of egress must extend from all accessible portions of a room or space. The IBC specifies maximum travel distances to reach an exit. Accessible means of egress can share a common path of egress travel as allowed for means of egress by the applicable building or life safety code (§207.1). The IBC (2003) permits one accessible ...

  6. Travel Distance

    The closest slope of an exit access ramp. An exit. In facilities with open-air assembly seating of Type III, IV or V construction, the total exit access travel distance to one of the following shall not exceed 400 feet (122 m): The closest riser of an exit access stairway. The closest slope of an exit access ramp. An exit.

  7. PDF U.S. ACCESS BOARD TECHNICAL GUIDE Accessible Means of Egress

    travel distance to an exit is short and the occupant load is low. For example, a business occupancy with no more than 30 occupants and a maximum exit access travel distance of 75 feet is permitted to have a single means of egress. More than two means of egress are required where the occupant load is 500 or more (at least 3) and 1,000 or

  8. PDF Accessible Means of Egress

    the interior travel distance (to the exit) is short and the occupant load (number of people that could be using the space) is low. For example, in a mercantile space, a single means of egress is permitted when there are fewer than 50 calculated occupants in the space or the exit access travel distance is less than 75 feet.

  9. PDF CHAPTER 10 MEANS OF EGRESS

    STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR R-2 OCCUPANCIES STORY OCCUPANCY MAXIMUM NUMBER OF DWELLING UNITS MAXIMUM EXIT ACCESS TRAVEL DISTANCE Basement, first, second or third story R-2a, b 4 dwelling units 125 feet Fourth story and above NP NA NA For SI: 1 foot = 304.8 mm. NP - Not Permitted NA - Not Applicable a.

  10. Digital Codes

    The closest riser of an exit access stairway. 1.2. The closest slope of an exit access ramp. 1.3. An exit. 2. In facilities with open-air assembly seating of Type III, IV or V construction, the total exit access travel distance to one of the following shall not exceed 400 feet (122 m): 2.1. The closest riser of an exit access stairway. 2.2.

  11. Basics of Means of Egress Arrangement

    Means of egress design must consider the distance occupants travel to an exit, how far apart exits are located from one another, and more.

  12. Egress travel distance for two exits

    In order to reach the second exit, they need to back track the 100 ft to where the common path of egress ended, and then travel 125 ft in the opposite direction to reach the second exit. Both exits are within the max travel distance of 200 ft, but the actual total distance traveled is 75 + 100 + 100 back track + 125 for a total of 400 ft.

  13. The IBC's modification to exit access travel distance

    The 2015 International Building Code includes a key modification, increasing the length of exit access travel distance from 250 ft to 400 ft (if it meets specific criteria) for buildings containing Group F-1 and/or S-1 occupancy. This change is significant to the design industry, building owners and occupants of large distribution and ...

  14. Single-Exit Buildings

    3408.4.4.1.1 Single-Exit Buildings. The occupant load, number of dwelling units and exit access travel distance do not exceed the values in Table 3408.4.4.1.1 (1) and Table 3408.4.4.1.1 (2). The occupant load is not greater than 10 and the exit access travel distance within the unit does not exceed 75 feet (22 860 mm).

  15. Jonathan Ochshorn—ARCH 2614/5614

    exit discharge (which leads to the public way) Review: Table 1020.1 Corridor Fire-resistance rating Table 1017.2 Exit access travel distance. There are no maximum distances between exits, except as determined by maximum exit access travel distances (which only require that any space be limited in distance from ANY ONE exit).

  16. 2015 International Building Code (Ibc)

    Exit access doorways shall be separated by a horizontal distance equal to one-half the maximum horizontal dimension of the room. All portions of machinery rooms shall be within 150 feet (45 720 mm) of an exit or exit access doorway. An increase in exit access travel distance is permitted in accordance with Section 1017.1.

  17. Measurement of Travel Distance to Exits

    The travel distance to an exit shall be measured on the floor or other walking surface as follows: Along the centerline of the natural path of travel, starting from the most remote point subject to occupancy. Curving around any corners or obstructions, with a 12 in. (305 mm) clearance therefrom. Terminating at one of the following:

  18. PDF Egress Common Path of Travel and Travel Distance

    Exit-Access Travel Distance § 1017 and Table 1017.2 provide the maximum length of exit-access travel distances, measured from the most remote point in the exit-access space to the entrance to an exit along a "natural and unobstructed path of egress travel. Egress distances are measured in the exit access space under consideration.

  19. Digital Codes

    1.2. The closest slope of an exit access ramp. 1.3. An exit. 2. In facilities with open-air assembly seating of Type III, IV or V construction, the total exit access travel distance to one of the following shall not exceed 400 feet (122 m): 2.1. The closest riser of an exit access stairway. 2.2.

  20. Chapter 10 Means of Egress: Means of Egress, California ...

    For the travel distance limitations and number of exit and exit access requirements for rooms and spaces in Group I-2 or I-2.1, see Section 407.4. The common path of egress travel distance shall only apply in a Group R-3 occupancy located in a mixed occupancy building.

  21. 2021 International Building Code (Ibc)

    Group B, F and S occupancies in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall have a maximum exit access travel distance of 100 feet. c. This table is used for R-2 occupancies consisting of sleeping units. For R-2 occupancies consisting of dwelling units, use Table 1006.3.4(1). d.